5
Cases Where 3-Phase Motors
May Run Single
Phase
If a one phase conductor supplying a 3-phase running motor is opened the motor usually continues to run as a single-phase machine. But current drawn by the operating phase is greater than design conditions for the winding. You may not discover single-phasing until the winding is damaged. Under some conditions, you may not recognize it at all. Preventing trouble is simple: use overload protectors in all three phases.
Typical Single-Phase
Conditions
Motor-circuit fuse blows or circuit
opens because of burned connection, worn switch contacts, etc. and motor goes on
running. Two overload relays are sufficient to protect the motor. You can use
suitable dual-element fuses instead of relays. This trouble often occurs because
relay heaters selected are too high, or have been tampered with or neglected.
Check relays regularly.

Open Primary
Phase
Where transformers are connected wye-delta
or delta-wye and have isolated neutral, they can cause severely unbalanced
3-phase current in motor. Current in one phase sometimes runs as much as twice
that in others. If high phase lacks relays, like B (below), motor keeps on
running until winding is damaged. Or on starting attempts, damage may be done
before overload relays trip.

Unbalanced Primary
Voltage
With delta-wye, wye-delta transformers
can also be a trouble source. A 2% voltage unbalance in one phase of primary can
cause 15% over current in one motor phase. If this phase is the unprotected one
of a heavily loaded motor, winding can be damaged. Voltage unbalance isn't rare,
so three relays are in order where you use this transformer connection.

Shunted
Single-Phase Load
The shunted single phase load
can produce unbalanced currents in a motor when one line is opened. Depending on
magnitude of shunted load and load on motor, one motor may carry current high
enough to damage the winding. This is another case where detection may not be
easy, so avoid trouble with a third relay. Most modern starters provide plenty
of space for easy installation of third relay.

Parallel 3-Phase
Motors
Parallel 3 phase motors that are
supplied from the same source can exchange current under some circumstances when
one line is open. Larger motor, No. 1 below, will supply unbalanced 3-phase
current to smaller motor, No. 2. Motor No. 2 may even be able to start. But one
phase will carry overload while other two lines carry about normal current or
lower, so again damage may result to unprotected phase.