Frequently Asked Questions & Answers

Alarm Trip & Temperature Settings

Question: What do you recommend as alarm and shut-down temperature settings for winding RTD’s?

Answer: The following tables (Tables 1 and 2) show alarm and shut-down temperatures based on the motor service factor, HP rating, and class of temperature rise. These temperatures apply to both winding RTD’s and thermocouples. See winding termperature detectors section for alarm / shut-down temperatures of thermostats and thermistors.

 Table 1: Monitors With Alarm and Shutdown

TEMPERATURE IN ° C

Insulation

CLASS A

CLASS B

CLASS F

Rating

Alarm

Trip

Alarm

Trip

Alarm

Trip

1.0SF<1500HP

110

120

130

140

155

165

1.0SF>1500HP

105

115

125

135

150

160

1.15SF<1500HP

120

130

140

150

160

165

1.15SF>1500HP

115

125

135

145

160

165

 

Table 2: Monitors With Shutdown Only

INSULATION

TEMPERATURE IN ° C

RATING

CLASS A

CLASS B

CLASS F

1.0SF<1500HP

110

130

155

1.0SF>1500HP

105

125

150

1.15SF<1500HP

120

140

160

1.15SF>1500HP

115

135

160

 